시험덤프
매달, 우리는 1000명 이상의 사람들이 시험 준비를 잘하고 시험을 잘 통과할 수 있도록 도와줍니다.
  / CFPS 덤프  / CFPS 문제 연습

NFPA CFPS 시험

Certified Fire Protection Specialist (CFPS) 온라인 연습

최종 업데이트 시간: 2025년06월06일

당신은 온라인 연습 문제를 통해 NFPA CFPS 시험지식에 대해 자신이 어떻게 알고 있는지 파악한 후 시험 참가 신청 여부를 결정할 수 있다.

시험을 100% 합격하고 시험 준비 시간을 35% 절약하기를 바라며 CFPS 덤프 (최신 실제 시험 문제)를 사용 선택하여 현재 최신 102개의 시험 문제와 답을 포함하십시오.

 / 5

Question No : 1


What percent of fire departments surveyed participate in the delivery of emergency medical services?

정답:
Explanation:
79% of fire departments surveyed participate in the delivery of emergency medical services (EMS). This is based on the NFPA report “US Fire Department Profile 2020” 1, which states that nationwide, 37% of fire departments provided no EMS, 46% provided basic life support (BLS), and 17% provided advanced life support (ALS). Therefore, the percentage of fire departments that provided either BLS or ALS is 46% + 17% = 63%. However, this does not include fire departments that provided EMS through a third-party contract or agreement. According to the NFPA fire service survey from 2018C 2020 2, 16% of fire departments reported having such an arrangement. Therefore, the percentage of fire departments that participated in the delivery of EMS in some form is 63% + 16% = 79%.
Reference: NFPA report - U.S. fire department profile 3
US Fire Department Profile 2020 Supporting Tables 2

Question No : 2


Which of the following NFPA Standards governs wiring for fire alarm systems?

정답:
Explanation:
NFPA 70, National Electrical Code (NEC), is the NFPA standard that governs wiring of a fire alarm system. NFPA 70 covers the general requirements for the design, installation, and inspection of electrical wiring and equipment, including fire alarm circuits and devices. NFPA 70 does not cover the performance of a fire alarm system, which is addressed by NFPA 72, National Fire Alarm and Signaling Code. NFPA 72 covers the application, installation, location, performance, inspection, testing, and maintenance of fire alarm systems and their components. NFPA 73, NFPA 75, and NFPA 76 are other NFPA standards that are related to fire alarm systems, but they do not specifically govern wiring. NFPA 73 covers the electrical inspection of existing dwellings. NFPA 75 covers the protection of information technology equipment. NFPA 76 covers the fire protection of telecommunications facilities.
Reference: NFPA 72 FAQs 1
National Fire Alarm and Signaling Code® - NFPA 2
TECHNICAL SERVICES DEPARTMENT BULLETIN - NEMA 3

Question No : 3


Which pure metal in its solid form in oxygen has the highest ignition temperature in degrees Fahrenheit?

정답:
Explanation:
titanium is the pure metal in its solid form in oxygen that has the highest ignition temperature in degrees Fahrenheit. The spontaneous-ignition temperature of titanium in the solid phase (below melting) is about 3020°F (1660°C) 1. Aluminum, potassium, and zirconium have lower ignition temperatures in the solid phase, ranging from 1292°F (700°C) to 1652°F (900°C) 23.
Reference: IGNITION OF METALS IN HIGH PRESSURE OXYGEN 2 Combustion of Metals in Oxygen-Enriched Atmospheres 3 High-temperature oxidation and ignition of metals 1

Question No : 4


For combustion to take place, a combustible material, an oxidizing agent, and an ignition source are required. The exception is

정답:
Explanation:
Spontaneous combustion is the exception to the requirement of a combustible material, an oxidizing agent, and an ignition source for combustion to take place. Spontaneous combustion is a phenomenon in which a material can ignite without any external heat or flame, due to a chemical reaction within the material that generates enough heat to reach the ignition temperature. Spontaneous combustion can occur in certain materials that are prone to self-heating, such as oily rags, hay, coal, and compost. Spontaneous combustion is a type of smoldering combustion, which is a slow, low-temperature, flameless form of combustion.
Reference: Fire Protection Handbook, 20th Edition, Volume 1, Chapter 2, Section 2.2.1.1 1 NFPA 921: Guide for Fire and Explosion Investigations, 2021 Edition, Section 4.3.1 2

Question No : 5


Which OSHA regulation addresses storage and handling of liquefied petroleum gas?

정답:
Explanation:
OSHA regulation 1910.110 addresses storage and handling of liquefied petroleum gas (LPG). This regulation covers the general requirements for the design, construction, installation, operation, inspection, and maintenance of LPG systems, including containers, piping, valves, fittings, regulators, burners, and appliances. The regulation also specifies the safety precautions and procedures for the prevention of fire and explosion hazards involving LPG. The regulation applies to all employers who store, handle, or use LPG in their workplaces.
Reference: OSHA: 1910.110 - Storage and handling of liquefied petroleum gases 1
Nebula Safety: Storage & Handling of Liquefied Petroleum Gases (LPGs) 2

Question No : 6


Which type of plan review may provide information about a modification such as the removal of an abandoned underground flammable liquid tank?

정답:
Explanation:
An as built plan review is a type of plan review that may provide information about a modification such as the removal of an abandoned underground flammable liquid tank. An as built plan review is conducted after the construction or alteration of a building or system is completed and before the final approval or acceptance by the AHJ. An as built plan review verifies that the building or system conforms to the approved plans and specifications and complies with the applicable codes and standards. An as built plan review may also identify any changes or deviations from the original plans that occurred during the construction or alteration process, such as the removal of an underground tank.
Reference: NFPA 1: Fire Code, 2018 Edition, Section 1.12.8.1.1 1
Fire Protection Handbook, 20th Edition, Volume 1, Chapter 5, Section 5.2.3.4 2

Question No : 7


What type of standpipe system provides 2 1/2 in. (65 mm) hose connections at designated locations in a building for use by the fire department?

정답:
Explanation:
A Class I standpipe system provides 2 1/2 in. (65 mm) hose connections at designated locations in a building for use by the fire department. A Class I standpipe system is intended to supply water for fire fighting operations by trained personnel using hoses of 1 1/2 in. (40 mm), 1 3/4 in. (45 mm), or 2 in. (50 mm) nominal diameters. A Class I standpipe system is required to deliver a minimum flow rate of 250 gpm (946 L/min) at a minimum residual pressure of 100 psi (6.9 bar) at the most remote hose connection.
Reference: NFPA 14: Standard for the Installation of Standpipe and Hose Systems, 2019 Edition, Section 3.3.4.1 1 Fire Protection Handbook, 20th Edition, Volume 1, Chapter 8, Section 8.2.1.1 2

Question No : 8


Fire alarm systems audible appliances ratings are usually stated as a sound pressure level (SPL) at what distance?

정답:
Explanation:
Fire alarm systems audible appliances ratings are usually stated as a sound pressure level (SPL) at 10 ft (3.05 m) from the appliance. The SPL is measured in decibels (dB) and indicates the loudness of the sound produced by the appliance. The SPL at 10 ft (3.05 m) is used as a standard reference point for comparing different audible appliances and for designing fire alarm systems to meet the required audibility levels.
Reference: NFPA 72: National Fire Alarm and Signaling Code, 2019 Edition, Section 18.4.3.1 1 Fire Protection Handbook, 20th Edition, Volume 1, Chapter 7, Section 7.8.2.1 2

Question No : 9


Which type of fire alarm system transmits signals that are permanently recorded at a constantly attended supervising station located either at the protected premises or at another location of the property owner?

정답:
Explanation:
A central station system is a type of fire alarm system that transmits signals that are permanently recorded at a constantly attended supervising station located either at the protected premises or at another location of the property owner12. The supervising station monitors the signals from the initiating devices and notification appliances, and sends them to the fire department alarm communications center or other authorized agencies12. A central station system can also provide additional functions such as remote control, data logging, and communication with other systems3.
Reference: Fire Detection and Alarm Systems - IFSTA, Chapter 14, Section 617, “Supervising Station Alarm Systems”.
Off-Premises Signaling and Supervising Stations, “Off-premises signaling is a critical aspect of a fire alarm system because it allows signals from the system to be sent to a constantly attended location such as a monitoring center.”
Fire Alarm Initiation, Occupant Notification, and Monitoring Guide | NFPA, “Proprietary supervising station fire alarm system”.

Question No : 10


The ignition test method that exposes the specimen to a known heat flux from a tungsten-quartz heater is referred to as a

정답:
Explanation:
The cone calorimeter is an ignition test method that exposes the specimen to a known heat flux from a tungsten-quartz heater. The cone calorimeter measures the heat release rate, mass loss rate, smoke production, and other parameters of the specimen during the test. The cone calorimeter is widely used to evaluate the flammability and fire behavior of materials and products.
Reference: NFPA 557: Standard for Determination of Fire Loads for Use in Structural Fire Protection Design, 2017 Edition, Section 5.3.2.1 1
NFPA 556: Guide on Methods for Evaluating Fire Hazard to Occupants of Passenger Road Vehicles, 2019 Edition, Section 4.3.2 2
Fire Protection Handbook, 20th Edition, Volume 1, Chapter 3, Section 3.2.2.2 3

Question No : 11


How many additional switches or circuit breakers are allowed for a separate service?

정답:
Explanation:
According to NFPA 70: National Electrical Code (NEC) 2020 Edition, Article 230.71(A), each service shall have only one disconnecting means unless the requirements of 230.71(B) are met, which provide four specific service configurations. In each configuration, there shall be not more than six switches or sets of circuit breakers, or a combination of not more than six switches and sets of circuit breakers, per service grouped in any one location. Therefore, the maximum number of additional switches or circuit breakers allowed for a separate service is six.
Reference: NFPA 70: National Electrical Code (NEC) 2020 Edition, Article 230.71(A) and (B) 12 ElectricalLicenseRenewal.com, 230.71 Maximum Number of Disconnects 3

Question No : 12


The two major principles used to determine egress width are the

정답:
Explanation:
The two major principles used to determine egress width are the flow and the capacity method, according to the web search results I found for you. The flow method is based on the assumption that the movement of people in egress components is analogous to the flow of fluid in pipes, and that the flow rate depends on the density and velocity of the occupants. The capacity method is based on the calculation of the required egress width by multiplying the occupant load by a factor that represents the space needed for each occupant to exit safely12.
Reference: Minimum Corridor Width Requirements | Explained! - Building Code Trainer, “The required capacity of corridors shall be determined as specified in Section 1005.1, but the minimum width shall be not less than that specified in Table 1020.2. There are two thing to note in this code section. The first is the required capacity of the corridor and the second is the minimum width. This might be confusing at first but lets walk through this to better understand the code section. The required capacity of a
corridor is based on the total occupant load served by the corridor. This is determined by Section 1005.1. This is the first place you must look to determine the required width of the corridor. Then when you know what the required width of the corridor must be, go to Table 1020.2 to verify the minimum width required. After you have done this, compare the two numbers and go with the most restrictive. This means that the actual width of the corridor is to be the larger of the two widths. If the required width calculates to be less than the minimum width, then go with the minimum width. However if the required width calculates out to be greater than the minimum width, then the calculated required width becomes the minimum width.”
DECODED: Calculating the Egress Width of Door Openings - I Dig Hardware, “To determine the egress capacity of a door, or how many people a door will accommodate, divide the clear opening width of the door by 0.2 inches per occupant or 0.15 inches per occupant (see previous page to choose which factor to use).”

Question No : 13


Power for driving fire pumps is selected on the basis of reliability, adequacy, economy, and

정답:
Explanation:
The correct answer is
B. Safety is one of the criteria for selecting the power source for driving fire pumps, according to NFPA 20, Chapter 9.1.1.11. Reliability, adequacy, and economy are the other criteria mentioned in the same chapter. Efficiency, adaptability, and ecology are not explicitly stated as criteria in NFPA 20, although they may be considered as secondary factors in some cases.
1: Pump Installation: Everything About Electric and Diesel Driven Fire …

Question No : 14


When should the data of a pre-incident plan be evaluated?

정답:
Explanation:
The data of a pre-incident plan should be evaluated after an incident, as part of the post incident critique or analysis. This is to assess the accuracy, completeness, and usefulness of the pre-incident
plan, and to identify any changes or updates needed based on the lessons learned from the incident. Evaluating the pre-incident plan after an incident can also help improve the emergency response performance and the fire safety management of the site.
Reference: 123

Question No : 15


When using the Fire Safety Concept Tree to assess life safety for occupancies, the major categories of strategies include managing the fire, managing exposed occupants, and

정답:
Explanation:
The Fire Safety Concept Tree is a tool for systematically evaluating the fire safety performance of a building or occupancy. It consists of three main branches: fire prevention, fire protection, and fire safety management. Fire prevention aims to eliminate or reduce the occurrence of fire. Fire protection aims to control or limit the fire development and spread, and to protect the exposed occupants and property. Fire safety management aims to ensure the effective operation and maintenance of the fire safety systems and the appropriate human behavior in case of fire. Emergency response is one of the subcategories of fire protection, which includes the actions of the fire department, the building staff, and the occupants to respond to the fire emergency.
Reference:

 / 5
NFPA